Alarma de fuga de refrigerante en sala de máquinas
Data center computer room refrigerant leak gas alarm. Common refrigerants used in data center precision air conditioners: R134a, R410A, R32, R454B, etc. Refrigerant leaks can displace oxygen and cause personnel suffocation; R32 is also weakly flammable. The refrigerant leak alarm consists of on-site detectors plus an alarm controller, enabling 24-hour online monitoring, audible and visual alarms, linked exhaust ventilation, and integration with dynamic environment monitoring systems. I. Sensor principle selection (computer rooms prioritize NDIR infrared) NDIR non-dispersive infrared (first choice) Strong anti-interference, 8-10 year lifespan, low drift, unaffected by temperature, humidity, or dust