机房氟利昂泄漏监测
Data Center Computer Room Refrigerant Leak Gas Alarm System Common Refrigerants Used in Data Center Precision Air Conditioners: R134a, R410A, R32, R454B, etc. Refrigerant leaks can displace oxygen and cause personnel suffocation; R32 also has weak flammability. The refrigerant leak alarm system consists of on-site detectors plus an alarm controller, enabling 24-hour online monitoring, audible and visual alarms, linked exhaust ventilation, and integration with dynamic environment monitoring systems. I. Sensor Principle Selection (Computer rooms prioritize NDIR infrared) 1. NDIR Non-Dispersive Infrared (First Choice) Strong anti-interference, lifespan of 8-10 years, minimal drift, unaffected by temperature, humidity, or