Data Center Refrigerant Leak Gas Alarm
Data center computer room refrigerant leak gas alarm. Common refrigerants used in data center precision air conditioners: R134a, R410A, R32, R454B, etc. Refrigerant leakage can displace oxygen and cause personnel suffocation. R32 is also weakly flammable. The refrigerant leak alarm consists of on-site detectors + an alarm controller, enabling 24h online monitoring, audible and visual alarms, linked exhaust ventilation, and integration with dynamic environment monitoring systems. I. Sensor principle selection (computer rooms prioritize NDIR infrared) NDIR non-dispersive infrared (first choice) Strong anti-interference, 8-10 year lifespan, low drift, unaffected by temperature, humidity, dust