数据中心机房冷媒泄漏气体报警器
Common refrigerants used in precision air conditioning for data centers include R134a, R410A, R32, R454B, etc. Refrigerant leakage can displace oxygen and cause asphyxiation, and R32 is also mildly flammable. The refrigerant leak alarm system consists of on-site detectors plus an alarm controller, enabling 24-hour online monitoring, audible and visual alarms, linked exhaust ventilation, and integration with dynamic environment monitoring.

Número do modelo: SKA/NE-301( R 1 3 4 a )

Introdução do produto

数据中心机房冷媒泄漏气体报警器

数据中心精密空调常用冷媒:R134a、R410A、R32、R454B等,冷媒泄漏会挤占氧气造成人员窒息,R32 还具备弱可燃性,冷媒泄漏报警器由现场探测器 + 报警控制器组成,实现 24h 在线监测、声光报警、联动排风、对接动环监控。

一、传感器原理选型(机房优先 NDIR 红外)

  1. NDIR 非分光红外(首选) 抗干扰强、寿命 810 年、漂移小,不受温湿度、灰尘、清洗剂干扰;适配R134a/R410A/R32/R454B,数据中心主流方案。
  2. 电化学传感器:成本低,寿命 23 年,易漂移,需要频繁校准,不建议机房长期使用。
  3. PID 光离子:适合微量检漏,对部分冷媒选择性差,多用于便携式检漏仪。

量程建议:05000ppm,分辨率 1ppm;输出接口:420mA、RS485Modbus RTU,方便接入动环系统。

二、报警阈值(工程通用设置)

表格

级别

浓度

动作

一级预警

5001000ppm

弹窗提示,记录告警

二级报警

30005000ppm

声光报警,自动启动事故排风机

三级联锁

≥8000ppm

强声光,联动空调冷媒切断阀,上传动环告警

参考标准:GB 500192015、GB/T92372017、ISO5149 制冷安全规范。

三、安装布点关键要点

  1. 安装高度(看冷媒密度) 
    • R134a、R410A:气体重于空气,探测器距离地面0.30.6m安装。
    • R32(比空气轻):探测器装在吊顶下方0.30.6m,气体容易聚集顶部。
  2. 布点位置 
    • 重点:精密空调压缩机、冷媒阀门、法兰、软管接头、管路焊缝周边。
    • 单探测器有效覆盖半径≤7.5m;避开风机直吹、出风口、强电磁设备,预留校准检修空间。