Product Introduction
The terminal block uses military-grade spring-type screwless terminals, just press and plug to connect wires. Even without a screwdriver on site, wiring can be completed quickly, and it supports wire diameters of 0.2–1.5 mm.2;
Multiple temperature ranges such as -40~80℃, -35~35℃, -35~50℃, 0~50℃ can be set via DIP switch, and can be freely changed on site. Other ranges can also be customized;
Adopts dedicated EMC anti-interference components, can withstand strong electromagnetic interference on site, industrial-grade processing chip, wide application range;
The flange is equipped with a high-quality silicone sealing ring, which ensures the sealing between the device and the exhaust duct during installation, greatly reduces the leakage of gas in the exhaust duct, and ensures the accuracy of data measurement to the greatest extent.
| DC Power Supply (Default) | AC24V±20% or DC18~35V | |
| Power consumption | Voltage output | 0.1W |
| Accuracy (Default) |
Humidity | ±3%RH(60%RH,25℃) |
| Temperature | ±0.3℃(25℃) | |
| Transmitter element temperature and humidity resistance | -40℃~+80℃,0%RH~95%RH (non-condensing) | |
| Probe measures temperature | -40℃~+80℃ (default) | |
| Probe measures humidity | 0%RH-100%RH | |
| Long-term stability | Humidity | ≤1%RH/y |
| Temperature | ≤0.1℃/y | |
| Response time | Temperature | ≤25s (1m/s wind speed) |
| Humidity | ≤8s (1m/s wind speed) | |
| Output signal | Voltage output | 0~10V (default) 0~5V |
| Load capacity | 0-5V | Load ≥500Ω |
| 0-10V | Load ≥600Ω | |
DC-powered analog type:
| DC Power Supply (Default) | 10~30V DC | |
| Maximum power consumption | Current output | 1.3W |
| Voltage output | 1.3W | |
| Accuracy |
Humidity | ±3%RH(60%RH,25℃) |
| Temperature | ±0.5℃(25℃) | |
| Transmitter circuit operating temperature and humidity | -40℃~+60℃, 0%RH~95%RH (non-condensing) | |
| Probe measures temperature | -40℃~+80℃ | |
| Probe measures humidity | 0%RH-100%RH | |
| Long-term stability | Humidity | ≤1%RH/y |
| Temperature | ≤0.1℃/y | |
| Response time | Temperature | ≤25s (1m/s wind speed) |
| Humidity | ≤8s (1m/s wind speed) | |
| Output signal | Current output | 4~20mA |
| Voltage output | 0~5V/0~10V | |
| Load capacity | Voltage output | Output resistance ≤500Ω |
| Current output | ≤600Ω | |

Main Application Areas
- HVAC Systems — Monitors temperature and humidity in air ducts for efficient climate control.
- Industrial Process Control — Ensures precise environmental conditions in manufacturing processes.
- Cleanrooms — Maintains strict temperature and humidity levels for contamination control.
- Pharmaceutical Storage — Provides reliable monitoring for sensitive drug storage environments.
- Greenhouses — Optimizes growing conditions by tracking duct air temperature and humidity.
Keywords:duct temperature humidity transmitter, industrial humidity sensor, HVAC temperature sensor, 4-20mA humidity transmitter, 0-10V temperature transmitter, duct mounted sensor, high accuracy humidity sensor, industrial parts supplier