• Detected gas: Freon (refrigerant, R22/R134a/R410A optional)

• Measuring range: 0~1000ppm

• Resolution: 1ppm

• Alarm point: 500ppm (customizable)

• Accuracy: ±3%FS

• Response time: T90 ≤30s

• Zero drift: ≤±2%FS/year
 

Product Model: SKA/FLA-BJQ

Product Introduction

Point-type Freon Alarm for Fixed Safety Monitoring in Chemical Cold Storage - Product Overview
The point-type Freon alarm is a fixed gas detection device used for fixed safety monitoring in chemical cold storage. Search keywords: point-type Freon alarm, fixed safety monitoring in chemical cold storage, Freon alarm. The alarm is fixedly installed in cold storage and can continuously detect Freon concentration. When the concentration exceeds the set threshold, it emits sound and light alarms and outputs switch signals to link exhaust or cut off refrigeration equipment. In fixed safety monitoring for chemical cold storage, point-type Freon alarms can reflect on-site gas risks in real time and prevent suffocation and explosion accidents.

Point-type Freon Alarm for Fixed Safety Monitoring in Chemical Cold Storage - Working Principle
Point-type Freon alarms typically use semiconductor sensors or infrared sensors to detect Freon concentration and output electrical signals to calculate gas concentration. In fixed safety monitoring for chemical cold storage, point-type Freon alarms convert detection signals into 4-20mA, RS485, or Modbus outputs, which can be connected to PLC, DCS, and gas alarm control systems. The alarm is fixedly installed on cold storage walls or brackets, with protection ratings up to IP65 or IP66, suitable for low-temperature, high-humidity, and explosion-proof environments.

Point-type Freon Alarm for Fixed Safety Monitoring in Chemical Cold Storage - Application Scenarios
Point-type Freon alarms are widely used in chemical cold storage, refrigeration machine rooms, quick-freezing rooms, and cold storage rooms. In fixed safety monitoring for chemical cold storage, point-type Freon alarms can be fixedly installed near compressors, evaporators, condensers, and pipeline valves, as well as in personnel inspection passages. The alarms can be linked with exhaust fans, shut-off valves, and fire protection systems to achieve automatic handling. For large cold storage facilities, point-type Freon alarms can form a multi-point monitoring network and upload data uniformly to the control room.

Point-type Freon Alarm for Fixed Safety Monitoring in Chemical Cold Storage - Technical Advantages
Point-type Freon alarms have advantages such as fast response, good stability, and strong anti-interference ability. In fixed safety monitoring for chemical cold storage, point-type Freon alarms use industrial-grade sensors and explosion-proof housings, suitable for low-temperature, high-humidity, and flammable and explosive environments. The alarm supports sound and light alarms, remote output, and fault self-checking, and is easy to maintain. When selecting point-type Freon alarms, attention should be paid to detection range, accuracy, response time, explosion-proof rating, and output signals to ensure they meet the needs of fixed safety monitoring in chemical cold storage.