TS - TS-FTWI5Y model
Operating voltage: 12~36VDC
Measurement accuracy
Temperature: ±0.3℃ Humidity: ±3%RH
Long-term stability: temperature <0.04℃/year, humidity <0.05%RH/year
Resolution: 0.1℃, 0.1%RH
Output signal
RS485 interface: MODBUS-RTU protocol
Switch output: 1 passive switch contact, normally open or normally closed
Contact load < 2A/30VDC (0.5A/125VAC), max switching current 2A
Product introduction
I. Overview of TS-FTWI5Y wall-mounted temperature and humidity transmitter
※ TS-FTWI5Y modelWall-mounted temperature and humidity transmitteruses original imported temperature and humidity
sensing modules. With signal processing by a high-performance microcontroller, the overall performance is more
superior and long-term stability is more outstanding.
※ This series of transmitters adopts flexible wall-mounted installation, easy to use, outputs standard
MODBUS-RTU communication signals, easily building a cost-effective temperature and humidity
real-time remote monitoring system.
※ This series of products is an integrated temperature and humidity transmitter, widely used in building automation,
climate and HVAC signal acquisition, climate stations in museums and hotels, greenhouse
and pharmaceutical industries, etc.
II. Parameters of TS-FTWI5Y wall-mounted temperature and humidity transmitter
※ Temperature
Range: -40~80℃
Accuracy: ±0.3℃ (average over full range)
Power consumption: 15mA (typical)
Resolution: 0.1℃
Response time 6τ (63%): min=5s, max=30s
Long-term stability: <0.04℃/year
Temperature output signal: MODBUS-RS485 signal
※ Relative humidity
Range: 0~99.9%RH
Accuracy (including nonlinearity, hysteresis, and repeatability): ±3%RH
Factory calibration uncertainty:
±0.6%RH(0~40%RH) / ±1.0%RH(40~97%RH)
Response time (90%) in still air: 8s
Resolution: 0.1%RH
Long-term stability: <0.05%RH/year
III. Operating and storage environment of TS-FTWI5Y wall-mounted temperature and humidity transmitter
Operating ambient temperature: -40~+85℃
Operating ambient humidity: 0~99.9% non-condensing
Operating voltage: 12~36VDC
Storage temperature: 10 – 50°C (0 – 125°C peak)
Storage humidity: 20 – 60%RH
(Note: Unless otherwise specified, all parameters above are measured at 25℃)