Duct-type Temperature and Humidity Transmitter TS-FTDO4
Duct-type Temperature and Humidity Transmitter

Duct-type Temperature and Humidity Transmitter - TS-FTDO4

Temperature
Range: 0~+50°C / -20~+80°C / -40~+60°C (configurable)
Accuracy: ±0.3°C (average over full range)
Power consumption: 15mA (typical)
Resolution: 0.1°C
Response time 6τ(63%): min=5s, max=30s
Long-term stability: <0.04°C/year

Model: TS-FTDO4

Product Introduction

TS-FTDO4 Duct-type Temperature and Humidity Transmitter Product Parameters:

Temperature

Range: 0~+50°C / -20~+80°C / -40~+60°C (configurable)

Accuracy: ±0.3°C (average over full range)

Power consumption: 15mA (typical)

Resolution: 0.1°C

Response time 6τ(63%): min=5s, max=30s

Long-term stability: <0.04°C/year

Relative Humidity

Range: 0~100%RH

Accuracy (including nonlinearity, hysteresis, and repeatability): ±3%RH

Factory calibration uncertainty:

±0.6%RH(0~40%RH) / ±1.0%RH(40~97%RH)

Response time (90%) in still air: 5s

Resolution: 0.1%RH

Long-term stability: <0.05%RH/year

Temperature and humidity output signal: 4-20mA (load <250 OHM)

Operating and storage environment

Operating temperature: -40~+85°C

Operating humidity: 0~99.9% non-condensing

Operating voltage: DC15~36V (recommended DC24V)

Storage temperature: 10-50°C (0-125°C peak)

Storage humidity: 20-60%RH

(Note: All parameters above are measured at 25°C unless otherwise specified)