Duct-type Temperature and Humidity Transmitter - TS-FTDO4
Temperature
Range: 0~+50°C / -20~+80°C / -40~+60°C (configurable)
Accuracy: ±0.3°C (average over full range)
Power consumption: 15mA (typical)
Resolution: 0.1°C
Response time 6τ(63%): min=5s, max=30s
Long-term stability: <0.04°C/year
Product Introduction
TS-FTDO4 Duct-type Temperature and Humidity Transmitter Product Parameters:
Temperature
Range: 0~+50°C / -20~+80°C / -40~+60°C (configurable)
Accuracy: ±0.3°C (average over full range)
Power consumption: 15mA (typical)
Resolution: 0.1°C
Response time 6τ(63%): min=5s, max=30s
Long-term stability: <0.04°C/year
Relative Humidity
Range: 0~100%RH
Accuracy (including nonlinearity, hysteresis, and repeatability): ±3%RH
Factory calibration uncertainty:
±0.6%RH(0~40%RH) / ±1.0%RH(40~97%RH)
Response time (90%) in still air: 5s
Resolution: 0.1%RH
Long-term stability: <0.05%RH/year
Temperature and humidity output signal: 4-20mA (load <250 OHM)
Operating and storage environment
Operating temperature: -40~+85°C
Operating humidity: 0~99.9% non-condensing
Operating voltage: DC15~36V (recommended DC24V)
Storage temperature: 10-50°C (0-125°C peak)
Storage humidity: 20-60%RH
(Note: All parameters above are measured at 25°C unless otherwise specified)