Home chevron_right Sensors chevron_right Gas Sensor 
Explosion-proof Gas Transmitter AMT/RS-FPC-*-N01
Explosion-proof Gas Transmitter

Explosion-proof Gas Transmitter - AMT/RS-FPC-*-N01

Explosion-proof Gas Transmitter

Product Model: AMT/RS-FPC-*-N01

Product Introduction

The on-site power supply adopts 10~30V DC wide-voltage power supply, supports the detection of multiple gases, and the range can be customized;

 

The explosion-proof gas transmitter adopts imported first-tier brand electrochemical sensors, featuring rapid and sensitive response and strong anti-interference ability;

 

Adopts remote infrared remote control technology, and through our company's unique compensation algorithm and multi-stage standard gas calibration, it also has the characteristics of long lifespan, high precision, high repeatability and high stability;

 

Optional high-quality LCD display, values can be viewed directly on site, and can also be displayed clearly at night;

 

The product adopts a wall-mounted explosion-proof enclosure, which is easy to install, with protection grade IP66 (the cable outlet end requires the customer to provide a flameproof enclosure introduction device that meets the requirements of GB/T 3836.2 (such as an explosion-proof sealing joint) for use). It can be applied to harsh on-site environments.

Power supply 10~30V DC
Average Power Consumption 0.35W
Additional power consumption when alarm light is working: 1W
Output signal 485 type: 485 output (standard ModBus protocol)
Analog type: 4~20mA, 0~5V, 0~10V
4G type: 4G wireless transmission
Repeatability NH3/H2/CO(1000ppm)/H2S/NO2/SO2/O3/PH3/CH2O/CL2:≤2%
CO(2000ppm) :≤3%     O2/N2:≤1%
Stability CO(1000ppm)/H2S/H2/NO2/SO2/NH3/PH3/CL2 ≤2% signal value/month
O3/CH2O ≤7% signal value/year
CO(2000ppm)/O2/N2 ≤5% signal value/year
工作温度 H2/CO/H2S/NO2/SO2/O2/NH3/PH3/O3/CH2O/CL2/N2:-20~50℃
Working humidity NH3/H2/CO/H2S/NO2/SO2/O3/PH3/CH2O/CL2: 15~90%RH non-condensing
O2/N2: 5~95%RH non-condensing
Operating Pressure NH3/H2/CO(1000ppm)/H2S/SO2/O2/O3/PH3/CH2O/N2/CL2 90~110kPa
NO2 91~111kPa
CO(2000ppm) 80~120kPa
Preheating Time NH3/H2/CO/H2S/NO2/SO2/O3/O2/PH3/CH2O/CL2: ≥5min
N2:≥15min
Explosion-proof marking Ex db IIC T6 Gb;Ex tb IIIC T80℃ Db
Relay load capacity 250VAC 1A/30VDC 1A
Measurement parameters of each element See Appendix A

 

Appendix A:

Gas name Optional range 分辨率 Accuracy Zero Drift Response time
O2 0-30 %VOL 0.1 %VOL ±2%FS ±0.3%VOL ≤10s
H2S 0-100 ppm 1 ppm ±2ppm or ±10% ±5ppm ≤35s
CO 0-1000 ppm 1 ppm ±5ppm or ±10% ±3ppm ≤30s
0-2000ppm 1 ppm ±5ppm or ±10% ≤±10ppm ≤30s
NO2 0-20 ppm 0.1 ppm ±5%FS ≤±0.5ppm ≤30s
0-2000 ppm 1 ppm ±5%FS ≤±20ppm ≤60s
SO2 0-20 ppm 0.1 ppm ±5%FS or ±10% ≤±0.5ppm ≤45s
0-2000 ppm 1 ppm ±5%FS or ±10% ≤±4ppm ≤70s
H2 0-1000 ppm 1 ppm ±5%FS ≤±10ppm ≤70s
NH3 0-50 ppm 0.1 ppm ±8% ≤±2ppm ≤90s
0-100 ppm 1 ppm ±8% ≤±2ppm ≤90s
O3 0-100ppm 1 ppm ±6%FS(@50ppm、25℃、50%RH) ≤±0.5ppm ≤30s
CH2O 0-5ppm 0.01ppm Accuracy: ±5%FS (@1ppm, 25℃, 50%RH) ≤±0.5ppm ≤35s
CL2 0~20ppm
0~50ppm
0.1ppm ±10% ±3%FS ≤60s
CL2 0~100ppm 1ppm ±10% ±3%FS ≤60s
N2 70~99.9%VOL 0.1%VOL ±0.6%VOL ±0.3%FS ≤10s